Metropolitan continental France (excluding Corsica and overseas) · updated 1 October 2026

In France a BESS earns on the hourly price spread more than on the grid-charge classes

Over the last year the day-ahead price was at or below zero for 757 hours and the daily 4-hour spread averaged 90 €/MWh, reaching 143 €/MWh in August 2026. The TURPE 7 energy charges, by contrast, differ by about 20 €/MWh between Pointe and HCB (HTA, long utilisation): a battery that follows the price is worth more than one that follows the classes.

67.6 €/MWhaverage day-ahead priceSMARD · 2025-09-01..2026-08-31
90 €/MWhdaily 4-hour spread
757hours at zero or negative price
× 4.54-hour spread vs TURPE Pointe–HCB gap (HTA LU)SMARD + CRE 2026-105 · 2026

Prices over the last year

Monthly average day-ahead price, €/MWh. Real history, no forecast.

35
57
59
69
101
46
64
40
52
66
95
123
SeptOctNovDecJanFebMarAprMayJunJulAug

Average daily spread

1012 hours
904 hours
718 hours

€/MWh: mean of the N most expensive hours minus the N cheapest of each day.

For commercial and industrial sites

At HTA level TURPE 7 has five time classes (Pointe, HPH, HCH, HPB, HCB): high season November to March, Pointe only December to February, and 8 off-peak hours a day set locally by the DSO, which Enedis is moving until end 2027. LV above 36 kVA has four classes without Pointe; suppliers usually price energy on the same classes, but the price is contractual.

Tariff band calendar

01234567891011121314151617181920212223
WeekdaysJan, Feb, Dec
HCH
HCH
HCH
HCH
HCH
HCH
HPH
HPH
HPH
P
P
HPH
HPH
HPH
HPH
HPH
HPH
HPH
P
P
HPH
HPH
HCH
HCH
WeekdaysMar, Nov
HCH
HCH
HCH
HCH
HCH
HCH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HPH
HCH
HCH
WeekdaysApr, May, Jun, Jul, Aug, Sept, Oct
HCB
HCB
HCB
HCB
HCB
HCB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HPB
HCB
HCB
Sunday and holidaysJan, Feb, Mar, Nov, Dec
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
HCH
Sunday and holidaysApr, May, Jun, Jul, Aug, Sept, Oct
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
HCB
PointeHPHHCHHPBHCB

Regulated charges by band

€/kWhEnergy
Pointe0.094
HPH0.071
HCH0.060
HPB0.064
HCB0.071

€/kWh. Energy: average day-ahead price in the band, last year.

Power charge

A power is subscribed for each class, non-decreasing from Pointe to HCB. With the same power in every class the charge is 41.86 €/kW/year at HTA and 35.74 €/kVA/year at LV above 36 kVA (LU option, 15 % CTA included): shaving only the winter peak saves little, the full charge is saved only by lowering all classes.

Value of exported energy

Exported PV captured 0.531 times the average price of 67.59 €/MWh over the last year, about 36 €/MWh before the aggregator fee. Plants up to 500 kW under the obligation d'achat have regulated tariffs instead, not shown here.

PV yield

1,140Nord
1,062 – 1,214
1,240Centre
1,190 – 1,281
1,485Sud
1,305 – 1,611

kWh/kWp per year, PVGIS 5.3, 30° tilt, south, 14 % losses.

For utility-scale storage

Revenue streams open to a storage plant and their status.

EPEX SPOT arbitrageactive

15-minute day-ahead since 1 Oct 2025 plus European intraday trading (SDAC/SIDC).

FCRactive

Procured by RTE through the FCR Cooperation daily auctions; prices not yet collected.

aFRR, mFRR, RRactive

RTE capacity auctions and European platforms (PICASSO for aFRR); storage prequalification rules to be checked.

Capacity mechanismactive

New design with RTE as single buyer: first auction on 6 Jul 2026 for winter 2026–2027 cleared at 28,182.99 €/MW (secondary source); battery derating not checked.

TURPE 7 injection-withdrawal componentactive

Optional for pure storage sites at HTA in selected grid zones: bonus or malus depending on whether charging and discharging help the grid.

Tenders and grantsabsent

As of 30 Sep 2026 no national storage tender or capex grant for C&I was found (search not exhaustive).

Rules

Summary of public rules. It does not replace the check of a qualified professional on the specific project.

Grid codedraft

Since 1 Jan 2025 Enedis applies the EN 50549 standards instead of VDE 0126: EN 50549-1 with EN 50549-10 tests at LV, EN 50549-2 at HTA under the arrêté of 9 June 2020 (RfG). The RfG type thresholds have not yet been read in the arrêté itself.

Self-consumptionverified

Individual and collective self-consumption (Code de l'énergie L. 315-1 and L. 315-2) allow storage. Zero export requires an anti-injection device and the Enedis self-producer without injection contract.

Connection and registryverified

Storage counts as consumption for its withdrawal capacity (40 % cost reduction) and as non-renewable production for injection (no reduction), unless associated with a renewable plant. Entry in the national registry follows the connection, with no separate filing.

Storage definitionverified

The Code de l'énergie (art. L. 352-1) defines storage as deferred use of electricity or its conversion and reconversion. For HTA storage the CRE requires flexible connection offers from 1 Aug 2026.

Fire safetydraft

No national rule specific to BESS. Above 600 kW of cumulated charging power on the site (EV chargers included) the installation is declared as ICPE 2925-2, with 5 m from the boundary and a hydrant within 200 m; a dedicated battery heading (2926) is in preparation.

Taxverified

Corporate income tax 25 %, no super-depreciation for BESS in 2026. Electricity charged into storage and fed back is exempt from excise; behind the meter, grid charging stays taxed with the site's consumption.

Products that can be used

On the Enedis grid a product must declare EN 50549-1 with EN 50549-10 tests at LV, or EN 50549-2 at HTA; VDE 0126 alone is no longer enough. List of systems in the barrel.center comparator that declare the country's grid code: in preparation.

Sources and data status

DataSourceDateStatus
Prices, spreads, negative hoursSMARD (Bundesnetzagentur), Großhandelspreise, filter 254 = France day-ahead, quarter-hour series, licence CC BY 4.0downloaded 2026-09-30verified
Time bandsSeason and class structure: CRE délibération 2025-40 (TURPE 7 HTA-BT, §4.3.1, tables 46-47) and Enedis-MOP-RES_088E; HC placement 22-6 h = CRE statement of TURPE 6 practice for HTA (same deliberation). Pointe hours 9-11/18-20 = assumption inside the statutory ranges.estimated
Regulated chargesCRE, délibération n° 2026-105 du 21 mai 2026, évolution du TURPE 7 HTA-BT au 1er août 20262026-05-21, grids in force 2026-08-01estimated
PV yieldPVGIS v5.3 (EU JRC) PVcalc APIqueried 2026-09-30verified
Grid codeEnedis-NMO-RES_025E v1 (ex Enedis-PRO-RES_10E v7), protections de découplage2025-09-15 (content v7 of 2025-01-01)draft
Fire safetyDGPR, fiche question/réponse IR_20241220_2925 (classement rubrique 2925, cumul des puissances y compris ESS)2025-01-15draft

Data from the public sources cited. 'Verified' means a primary source, 'draft' a secondary source or a rule not read in full. Not advice: a project needs the site's and the contract's data.